| CONSTRUCTION: |
| Conductor: |
Horizontal Cable: 1 x 24AWG (1/0.5mm) solid copper or |
| Patch Cable: 7 x 32AWG (7/0.2mm) stranded coppers |
| Insulation: |
HDPE |
| Colour Code: |
Pair 1:White/Blue & Blue, Pair2:White/Orange & Orange |
| Pair 3: White/Green & Green, Pair4: White/Brown & Brown |
| Jacket: |
LSZH, Nominal OD: Horizontal cable - 5.2mm; Patch cable - 5.6mm |
| Standards: |
TIA/EIA-568B.2, Horizontal Cable (solid copper) |
| TIA/EIA-568B.2, Patch Cable (stranded coppers) |
|
|
| |
| PRODUCT PART NUMBER |
| URO45e-LSZH-305-XX: |
UTP Cat. 5e 4P 24AWG Horizontal/Solid(1/0.5mm) cable in LSZH Jacket, XX(Jacket Colour), 305M/1000FT per Box |
| URT45e-LSZH-305-XX: |
UTP Cat. 5e 4P 24AWG Patch/Stranded(7/0.2mm) cable in LSZH Jacket, XX(Jacket Colour), 305M/1000FT per Box |
| XX : Jacket Colour Code: |
GY: Gray, YW: Yellow, GR: Green, PK: Pink, VL: Violet, |
| BL: Blue, OR: Orange, WH: White, BK: Black, RD: Red |
| e.g. URO45e-LSZH-305-GY: UTP Cat. 5e 4P 24AWG Horizontal/Solid(1/0.5mm) cable in LSZH Jacket, Gray Colour, 305M/1000FT per Box |
|
| |
TIA/EIA-568B.2 Category 5e Transmission Requirements |
Horizontal cable |
|
Att. |
Pr-Pr NEXT |
PS |
Prop. |
Delay |
Return Loss |
Pr-Pr ELFEXT |
PS |
MHz |
Solid |
NEXT |
Delay ns |
Skew ns |
ELFEXT |
1 |
2 |
65.3 |
62.3 |
538.5 |
45 |
20 |
63.8 |
60.8 |
10 |
5.9 |
50.3 |
47.3 |
545 |
45 |
25 |
43.8 |
40.8 |
16 |
8 |
47.3 |
44.4 |
539.9 |
45 |
25 |
39.7 |
36.7 |
20 |
9.2 |
45.8 |
42.8 |
540.2 |
45 |
25 |
37.7 |
34.7 |
25 |
10.6 |
44.4 |
41.3 |
540.8 |
45 |
24.3 |
35.8 |
32.8 |
31.25 |
11.7 |
42.9 |
39.9 |
541.4 |
45 |
23.6 |
33.9 |
30.9 |
62.5 |
17 |
38.4 |
35.4 |
542.5 |
45 |
21.5 |
27.8 |
24.8 |
100 |
22 |
35.3 |
32.3 |
543 |
45 |
20.1 |
23.8 |
20.8 |
Patch cable |
Frequency |
Att. |
Pr-Pr NEXT |
PS |
Prop. |
Delay |
Return Loss |
Pr-Pr ELFEXT |
PS |
MHz |
Stranded |
NEXT |
Delay ns |
Skew ns |
ELFEXT |
1 |
2.4 |
65.3 |
62.3 |
538.5 |
45 |
20 |
63.8 |
60.8 |
10 |
7.4 |
50.3 |
47.3 |
545 |
45 |
25 |
43.8 |
40.8 |
16 |
9.5 |
47.3 |
44.4 |
539.9 |
45 |
25 |
39.7 |
36.7 |
20 |
10.7 |
45.8 |
42.8 |
540.2 |
45 |
25 |
37.7 |
34.7 |
25 |
12.1 |
44.4 |
41.3 |
540.8 |
45 |
24.2 |
35.8 |
32.8 |
31.25 |
13.7 |
42.9 |
39.9 |
541.4 |
45 |
23.3 |
33.9 |
30.9 |
62.5 |
20 |
38.4 |
35.4 |
542.5 |
45 |
20.7 |
27.8 |
24.8 |
100 |
26.1 |
35.3 |
32.3 |
543 |
45 |
19 |
23.8 |
20.8 |
|
| Electric Requirements: (Cable length: 100M) |
| Characteristic Impedance(Zo): 85~115Ω (1~100 MHz) |
| Other Requirements: (dB/100M) |
| DC. Resistance Capacitance Unbalance: 5% |
| Pair-to-Ground Capacitance Unbalance: 330 pF/100M Max |
| Conductor Resistance: Horizontal cable - 9.38Ω/ 100M 20℃ Max ; Patch cable - 8.76Ω/100M 20℃ Max |
| Mutual Capacitance: 5.6 nF/m Max |
| Spark Test: 2.5KV |
| N.V.P: 69% |
|
|